Ethernet Driver For Gateway Profile 5
SLC 5/05 Ethernet RSLinx Driver Communication Setup - PLCS.net - Interactive Q & A
Member
Join Date: Jan 2006
Location: Albany, NY
Posts: 36
SLC 5/05 Ethernet RSLinx Driver Communication Setup
I recently bought a SLC 5/05 CPU and am trying to communicate with the Ethernet port for configuring it. I can communicate using the DF-1 port, however I will soon be using this port for communication to a PanelView 900 so I need to use the Ethernet one for configuration and troubleshooting. Here are my settings for the SLC 5/05:
IP Address: 192.168.1.2
Subnet Mask: 255.255.255.0
Gateway Address: 0.0.0.0
Bootp Disabled
Here are my settings for the laptop I m using:
IP Address: 192.168.1.1
Default Gateway: None
No Firewall
I also have a crossover cable going from the PC to the SLC. When I configure the Ethernet driver in RSLinx, I add 192.168.1.2 to Station 0 and then try to browse it. It browses it and sees it but shows it as an Unrecognized Device and will not communicate with it. I also pinged the PLC from the command prompt and received successful replies from it. I thought it could be a software issue because we do have RSLogix 500 and RSLinx versions that are older. We have RSLogix 500 Version 5.20.00 Build 17 and RSLinx Lite Version 2.31.00 Build 10. However, I talked to another engineer who uses the same versions and in a previous project, was able to communicate with a SLC 5/05 through an ethernet switch.
Am I missing something here. I m not quite sure where else to go to troubleshoot this. Any help would be appreciated. Thanks.
Pete.
ORing is mainly focus on the products of Industrial Ethernet Switch, Industrial Serial Device Server and Industrial Wireless products. With the integration of our.
Intel Quark processors. Intel Quark SoCs combine high levels of integration, low power, and reduced cost, with rich I/O capabilities ideally suited for the.
Nov 22, 2013 Following the overwhelming success of Industrial Ethernet Facts and taking into account continued development of the protocols, this overview of the key.
- EtherNet/IP to PROFINET IO Device Gateway PLX31-EIP-PND. The EtherNet/IP to PROFINET IO Device slave gateway offers bi-directional data transfers between.
- ORing Industrial Networking Corp. the global leading brand company, established in 2005 and focuses on innovation of Industrial networking products.
- How to Install Network Adapter Drivers. Network adapters are sometimes called network interface cards NIC or Ethernet adapters. The port in the adapter is your.
- Devices that Work with usbnet Here s an incomplete list of devices that the usbnet driver works with. It s incomplete because Linux doesn t need to know anything.
DeviceMaster LT16. The RS-232/422/485 software-selectable DeviceMaster LT16 device server is designed for network-enabling serial communications devices.
PLX31-EIP-PND
The EtherNet/IP to PROFINET IO Device slave gateway offers bi-directional data transfers between EtherNet/IP controllers and a PROFINET IO controller. The EtherNet/IP Driver supports I/O connections for guaranteed data delivery or Message instructions to send data to/from the PACs. The gateway supports 1440 bytes of input data and 1440 bytes of output data for larger applications.
In addition, the gateway s multiple I/O connections, allow you to set different RPIs for control data and module diagnostics, enabling you to optimize your Ethernet bandwidth.
Architectures
Drag with the mouse. Click for close.
Features and Benefits
Embedded EDS Add-On Profile allows for simplified integration and reduced configuration time for Rockwell Automation PACs.
No ladder programming is required when using I/O connections.
Multiple I/O connections allow you to set different RPIs for status and control data, enabling Ethernet bandwidth optimization.
Communication via an I/O connection provides guaranteed data delivery and enables the PAC to monitor for communication faults.
SD card slot SD card optional is used for storing configuration files in the event of a disaster.
ProSoft Discovery Service allows your PC to find the gateway and change its default IP address without being on the same subnet.
Video setup tutorial provided at psft.com/Ap5
Specifications
Number of Class 3 Server Connections
Supported PLC Types
PLC2, PLC5, SLC, CLX, CMPLX
Supported Message Types
PCCC and CIP
Number of Class 3 Client Connections
Connected - 2
Unconnected - 1
Number of Class 1 I/O Connections
Max I/O connection sizeIn/Out
496/496 bytes
Max RPI time
10 ms per connection
CIP Services Supported
0x4C - CIP Data Table Read
0x4D - CIP Data Table Write
Command List
Support for 100 commands per Client, each configurable
for command type, IP address, register to/from addressing
and word/bit count.
Command Sets
PLC-2/PLC-3/PLC5 Basic Command Set
PLC5 Binary Command Set
PLC5 ASCII Command Set
SLC500 Command Set
Hardware Specifications
Power Supply
24 VDC nominal
10 to 36 VDC allowed
Positive, Negative, GND Terminals
Current Load
24 VDC nominal 300 mA
10 to 36 VDC 610 mA maximum
Operating Temperature
-25 C to 70 C -13 F to 158 F
Storage Temperature
-40 C to 80 C -40 F to 176 F
Shock
IEC 60068-2-27; 15G 11ms, 3-Axis Operational
IEC 60068-2-27; 30G 18ms, 3-Axis Non-Operational
Vibration
IEC 60068-2-6; 5G 10 to 150 Hz
Relative Humidity
5 to 95 RH with no condensation
Dimensions H x W x D
5.38 x 1.99 x 4.38 in
13.67 x 5.05 x 11.13 cm
LED Indicators
Configuration CFG, Error ERR, Power PWR,
Hardware Fault FLT, Network Status NS,
EtherNet/IP Class I or Class III Connection Status
EtherNet/IP Only Module Status MS, ModuleConfiguration
Status EtherNet/IP Only Ethernet Communication
Port Link/Activity, and 100 mbit
Ethernet Port
10/100Mbit half-duplex RJ45 Connector Electrical Isolation
1500 Vrms at 50 to 60 Hz for 60 seconds, applied as
specified in section 5.3.2 of IEC 60950: 1991 Ethernet
Broadcast Storm Resiliency is less than or equal to
5000 ARP frames-per-second and less than or equal to
5 minutes duration
Shipped With Each Unit
2.5 mm screwdriver
ProSoft Solutions DVD
J180 Power Connector
5 straight-through Ethernet cable.